SECTION 7
Specific Considerations for Kitchen Extract
Systems
7.1
The kitchen extract system presents particular hazards due to the potential for
the accumulation of grease. Accumulated grease within an extract system forms a
hidden combustion load. Under certain circumstances flame or very high temperature
within the duct can ignite the grease causing fire to spread rapidly through
the duct. Flame and heat within the duct can ignite surrounding materials at
various points along the ductwork path and transfer fire in ways that are
difficult to predict and control by designers, installers and ultimately fire
fighters.
7.2
Kitchen extract ventilation systems are defined here as the extract systems
intended to collect and remove contaminants, heat and
moisture from cooking appliances (See also DW/172). A kitchen extract system
would typically comprise of the following components:-
Canopy
– Also referred to as hood, canopy hood, extraction hood, cooking hood,
cooker hood, cooking canopy or extraction canopy. This would most likely
include a vertical canopy skirt running around the perimeter of the canopy.
A“U’ channel on the bottom edge of the skirt; a canopy roof sitting
horizontally on the top of and joining the skirts; a grease filter housing assembly
(with grease filters and traps) hanging within the boundary of the skirts.
Canopy/Extract
plenum – This is typically the area immediately behind the grease filter housing
and below where the ducting commences.
Ducting
– Beyond the canopy/extract plenum, extraction ductwork would be connected.
This may involve short transition ducts connected directly to the suction side
of an extract fan or could include many linear metres of horizontal and/or
vertical ductwork. Vertical ductwork, also referred to as riser may pass
through many levels of a building. Contained within the ducting there may be
attenuators, flow control dampers, fire dampers, air turning vanes and sensors.
Extract
Fan – To create extraction from the canopy an extract fan would be
connected to the ductwork, some extract fans (roof mounted) discharge directly
to atmosphere via a cowl.
Discharge
Duct – On the exhaust side of the fan a discharge duct would direct extract
air out of the building via an outlet. This outlet point may include weather louvres and mesh to prevent the ingress of weather and
vermin. Other systems such as ventilated ceilings and directly ducted
extraction are also used. It is important that the person responsible for
implementing cleaning regimes clearly understands the breakdown of the system
so that any cleaning regime is compliant with the terms of buildings insurance
relevant to the kitchen extract maintenance.
7.3
Other extraction systems serving the cooking area, such as potwash/dishwash
systems, general extraction etc. may also be affected by grease deposits and
similar considerations will apply.
7.4
Kitchen extract systems are liable to internal fouling by grease and oils. It is
usual for the systems to be protected by grease filters, but these differ
widely in terms of efficiency of grease removal and of barrier to flame. Total grease
removal is not normally feasible and therefore fouling of systems downstream
will occur to a greater or lesser degree.
7.5
Grease deposits within systems also pose hygiene, odour, vermin and mechanical
efficiency hazards. Poorly designed and installed or damaged ductwork can leak
grease, thus extending the fire risk, hygiene, odour and vermin hazards. Also,
where ductwork distorts under fire conditions, burning grease can leak out and
spread the fire to duct surroundings.
7.6
Supply or make-up ventilation systems should be maintained in hygienic
condition as detailed in this Guide. Due to the accumulated grease within
extract systems, the majority of the duct - work cleaning will be by manual
rather than mechanical methods. At the time of system survey, a detailed
schematic should be provided, highlighting any areas which are inaccessible and
therefore, will remain uncleaned. The client must be
advised of any inaccessible areas, the reason for their inaccessibility and, if
possible, the likely cost to provide full and free access. It is the clients responsibility to highlight this to their insurer or
other relevant third party, if required, who must confirm whether an exception to
the total cleaning in accordance with TR/19 is acceptable.
7.7 This section of the Guide provides specific advice on how to clean and maintain kitchen extract systems, but similar consideration will apply to non-kitchen areas that might be affected by grease and/or oil deposits.
Design and Access to the Internal Surfaces
of the Kitchen Extract System
7.8
Advice is provided in HVCA DW/172: Specification for Kitchen Ventilation
Systems (2005).
7.9
Internal surfaces of kitchen extract systems should be free of irregularities,
all of which make grease accumulation more likely and cleaning more difficult.
7.10
It is essential that a kitchen extract ductwork system, and canopy/extract
plenum, is provided with access panels of sufficient number, quality and size
to enable unrestricted access for regular cleaning and inspection of the
internal surfaces and in-line components.
7.11
Location of access to the internal surfaces of a kitchen extract system is
dependent on a number of design and operational considerations
·
Design and location of ductwork
·
Building design and construction materials
·
Location of kitchen within the building
·
Location of extract fan and accessibility for
maintenance
·
Accessibility to physically reach the ductwork
·
Any building modifications and current uses that
may restrict access
·
Location and number of system components requiring
access.
7.12
Access panels should be suitable for the purpose for which they are intended.
The panels and frames should be constructed of the same material as the
ductwork. As a minimum they should incorporate quick release catches, sealing
gasket and thermal, acoustic and fire rated insulation properties equal to that
of the duct to which they are fitted. Particular consideration must be given to
maintaining the fire integrity of firerated ductwork.
The recommendations of the manufacturer or specialist fire protection adviser should
be followed where appropriate.
7.13
Access panels should be as large as the duct size permits to a maximum of 460mm
x 610mm without weakening the structure of the system. Openings should not be
obstructed by other building services, stored equipment or by the fabric of the
building. The panel and aperture should be free of any sharp edges.
7.14
Access panels should be fitted at the side of the duct, a minimum of 10mm above
the base to minimise the risk of grease leakage. Exceptionally, they may be
fitted on the top of the duct, but due consideration should be given to the
accessibility of the panel. Where access panels must be fitted to the underside
of a duct, particular care must be taken to ensure a leakfree
fit and notice should be affixed warning of the risk of oil being released on
opening the panels. In designing systems due consideration should be given to
providing physical unobstructed access to all access panels.
7.15 Access panels should be fitted on either side of in-line components, as detailed in Table 8, to allow physical entry to clean these intricate surfaces. This Table includes components, such as fire dampers and attenuators, which are not normally recommended to be installed, but are often found in practice.
|
Table
8: Location of Access Panels for Cleaning and Inspection Purposes |
|
|
Volume Control Dampers |
Both sides |
|
Fire Dampers (see Note 7) |
Both sides |
|
Attenuators |
Both sides |
|
Changes in Direction |
Both sides |
|
Filter Sections |
Both sides |
|
Horizontal Ducts |
Generally every 3 metres (see Note 2) |
|
Risers |
Top and bottom as a minimum (see Note 3) |
|
Extract Fans |
Both sides (see Note 4) |
|
Discharge grille/mesh |
One side (see Note 6) |
Notes to Table 8
1. Additional builders work hatches may need to be fitted
in ceilings/walls in existing installations, or provided for in new constructions.
Consideration should also be given to safe high level access to external ductwork.
2. Access openings for cleaning purposes are generally
required at a maximum of 3 metre centres and/or at each change of direction.
This distance should be reduced where the size of the duct prevents adequate cleaning
by hand, where there are several changes in direction or where other external
features restrict the positioning of panels.
3. Internal kitchen extract risers often require access
doors fitted on at least each floor level so that all internal surfaces can be reached
and fire dampers, where fitted, cleaned and checked. In older buildings this
may require additional builders works (e.g. hatches through brickwork) to reach
the riser ducts (see 7.6).
4. Extract fan design should allow thorough cleaning of
impellor blades and internal surfaces without the need for dismantling, i.e.
ductwork with access panels should be provided immediately upstream and
downstream. Larger fans should be designed with panels in the casing.
Similarly, attenuators or other in-line fittings likely to obscure cleaning
activity should be provided with access on both sides.
5 Guideline access frequency
given above may be reduced where remote cleaning methods and personnel entry
can be adequately applied. However, in all instances every section of ductwork
should be capable of verification inspection.
6 Design consideration should be
given to the provision of safe access to the downstream side of discharge
grilles, bird guard mesh and louvres.
7 Fire dampers are not fitted in new installations, but
may still be found in older systems.
7.16
During cleaning maintenance it is essential to ensure that the mechanical and
any fire integrity of access provision is maintained.
Access panels should be identified and marked on a schematic sketch (see
Verification of Cleanliness below). Control procedures should ensure that all
access panels are properly replaced after cleaning, and that any fire
protection removed for cleaning (e.g. cladding board) is properly re-fitted
both at the duct and at any builders work. The number of access panels removed
at any one time should be kept to a minimum. All panels should be replaced at
the end of the working shift.
7.17
Designers, installers or specialist cleaners should define and justify the
number of access panels to be fitted to an installation in line with this
Guide.
System Testing (Inspection/Monitoring)
7.18
The Health & Safety Executive and industry and insurance guidance and
regulations (see Appendices B & E) stipulate that kitchen extract systems
should be kept clean to minimise fire and other risks. This Guide now provides
a method of measuring and defining cleanliness and dirtiness as a benchmark for
good practice.
7.19
The HVCA Ventilation Hygiene Group Branch has investigated a variety of methods
for testing ductwork system internal surfaces to measure grease deposits and
recommends the Wet Film Thickness Test (W.F.T.T.) measurement method. This
method is described in Appendix D.3.
7.20
The Deposit Thickness Test (D.T.T), as described in Section 5, may also be used
and may be necessary in the case of extremely hardbaked,
carbonised, deposits. It is however less reliable for soft or liquid deposits
and the finding of hard-baked deposits would normally indicate a requirement to
clean or in the case of cleanliness verification a requirement to reclean.
7.21
The testing methods provide an objective, repeatable and verifiable measurement
of grease deposits, and overcome the subjectivity of visual inspection alone.
7.22
It is recommended that testing be carried out at intervals not exceeding 12
months. Monitoring of grease deposits may need to be carried out more
frequently if it is necessary to establish a precise definition of required
cleaning frequencies. The cleaning frequency required should be estimated by a
specialist service provider and/or client on initial inspection or assessment
and subsequent pre-clean testing will confirm whether the initial predicted
frequency is correct or requires adjustment.
7.23
Measurements should be taken at the following locations where practicable:
·
Canopy/Extract plenum behind filters
·
Duct 1 metre from canopy
·
Duct 3 metres from canopy
·
Duct midway between canopy and fan
·
Duct upstream of fan
·
Discharge duct downstream of fan
7.24
Table 9 sets out guideline maximum levels of grease deposit and actions
recommended. The actual recommended action timing will depend on the rate of
accumulation, the risk vulnerability of the system and site and any particular warranties
imposed by the building insurers.
|
Table
9: Surface Grease Deposit Limits |
|
|
Wet
Film Thickness Test Measurement |
Recommended
Action |
|
200μm as a mean across the system |
Complete cleaning required |
|
Any single measurement above 500μm |
Urgent local cleaning required |
Notes to Table 9
1. In the absence of, and the likely theoretical difficulties
of, an absolute measure of the flammability of various quantities of grease
deposit, the surface grease deposit limits are given in Table 9 and paragraph 7.42.
These levels were determined by extensive field testing to measure at what levels
good practice employers, or operators of systems, carry out system cleaning and
what levels of cleanliness are normally achieved by specialist duct cleaners
using available cleaning and measurement technology within reasonable economic bounds.
2. The deposit limits refer to the degree of grease
deposition within the ductwork consistent with good practice. Other factors such
as cooking methods, potential ignition sources, and other combustible debris
will affect the risk of fire.
3. The mean measurement is calculated by dividing the
total of the test results by the number of testing locations.
4. The second category of any single measurement above 500μm
is provided to cater for local “hot spots” which should be cleaned even where
the whole system does not require complete cleaning. Examples might be
immediately local to a canopy or at a fan
5. The extent of urgent local cleaning precipitated by the
presence of grease deposits above 500μm should be subject to reasonable appreciation
of the extent of fouling and risk posed.
7.25 The surface grease deposits limits should not be confused with the level set for Post - Clean verification which is far more stringent and detailed in paragraph
7.42.
7.26
Stand-alone, regular or post-clean testing can usefully be combined with
inspection of other kitchen extract system safety issues. If specified by a
client, a service provider should provide evidence of competence to carry out
such inspection. Such inspection should include, but not be restricted to:
1.
Adequacy of filters and their regular maintenance
2. Adequacy of regular cleaning of canopy, and associated drains and traps
3.
Existence and visual condition of any fire suppression or detection system
4.
Damage to fire protection
5.
Ductwork grease leakage
6.
Ductwork damage
7.
Damage to or inappropriate ductwork fixtures
8.
Visual/audible check of fan operation
9.
Rubbish/debris adjacent to system
10.
Visual assessment of any special filtration
11.
Discharge condition, including grease splatter/staining
7.27
Such inspection should not be regarded as a substitute for proper maintenance
of plant such as fans and fire suppression or detection systems.
Cleaning Methods
7.28
This guide is not intended to be definitive in relation to the method of
cleaning, as there are many existing methods that can be applied in tandem, and
emergent new technologies. Examples of cleaning methods are listed in Table 10.
7.29
To conform with the Guide, the actual method or
methods must be capable of achieving the required results, i.e. Post-Clean
Verification, not only on the internal surfaces of the extract duct but also on
system components.
7.30
When choosing the cleaning method, consideration should be given to operative
safety and also to effects on the surrounding environment, particularly where
using wet cleaning methods, since grease/moisture can leak from the ductwork components
and damage the surrounding fabric.
|
Table
10: Examples of Cleaning Methodology |
||
|
Generic Name |
Energy Source |
Removal Method |
|
Hand wipe |
Manual |
Wiping the surface of the ductwork |
|
Hand scrape |
Manual |
Removing heavy deposits by hand scraping |
|
Chemical |
Manual |
Softens or dissolves deposits making them suitable for hand scraping |
|
High pressure water wash (steam) |
Electrical or compressed air |
Vapour or liquid expelled at high pressure from lance to dislodge/dissolve deposits |
|
Blasting (remote or direct) using suitable
medium as appropriate |
Compressed air |
Blasting medium dislodges contaminant from
duct and component surfaces to be removed via vacuum techniques or high
volume filtered extraction. |
7.31
Steam cleaning and high pressure water washing are not recommended for ductwork
that is situated above false ceilings or in sensitive areas, due to possible
leakage of contaminants from the duct, unless specifically designed for wet
cleaning.
7.32
After applying wet cleaning methods care should be taken to ensure that any
condensed vapours and cleaning fluids are removed from all parts of the system.
7.33
The use of chemical cleaning agents should only be considered where a
risk/COSHH assessment has been carried out (See Section 10), the details
recorded and the effects of the applied chemicals have been assessed on the
material construction, environment and for hazards to cleaning personnel.
7.34
It should be noted that it is not normally economically practicable to clean
kitchen extract systems to a "like new" bright metal condition due to
substrate staining.
Frequency of Cleaning
7.35
The need for specialist cleaning of extract systems will depend on the level of
usage of the cooking equipment, types and quantity of cooking and other risk
factors such as vulnerability of the system to ignition and of the building and
its occupant/users to system fire, hygiene, vermin and mechanical hazards.
Typical cleaning intervals are shown in Table 11:
|
Table
11: Frequency of Cleaning |
||
|
Heavy Use |
12-16 hours per day |
- 3 monthly |
|
Moderate Use |
6-12 hours per day |
- 6 monthly |
|
Light Use |
2-6 hours per day |
- 12 monthly |
Note to Table 11
The
canopy and canopy/extract plenum is an area of higher fire risk and
consideration should be given to more frequent cleaning in accordance with
insurers’ requirements (see 7.39)
7.36
The frequency of cleaning should be adjusted by means of system testing
(inspection/monitoring) - see paragraph 7.23, so that surface grease deposit
limits in Table 9 are not exceeded. The buildings insurance company should be
consulted to ensure that the cleaning regime is compliant with the terms of
their specific warranty.
7.37
Any cleaning regime should be justified by a considered risk assessment. (The
latest Fire Precautions Workplace, and Management of Health
& Safety at Work Regulations apply).
7.38
Regular cleaning will result in an improved mean standard and reduce the costs
of cleaning as deposits are not allowed to bake and harden.
7.39
Periodic specialist cleaning should be accompanied by daily or weekly cleaning
of canopies, filters and associated drains and traps in accordance with
manufacturers' recommendations, typically carried out by the kitchen operator.
Post-Clean Verification of Cleanliness
7.40
The primary method of assessment is visual. For cleaned system verification,
the surface should be visibly clean and capable of meeting the level of
cleanliness specified.
7.41
Verification of cleanliness should be by means of the Deposit Thickness Test or
Wet Film Thickness Test as detailed in System Testing (Inspection/Monitoring)
at paragraph 7.23.
7.42
The level of cleanliness is that no single measurement should exceed 50μm
7.43
On completion a report should be provided containing the following:-
·
The system(s) cleaned
·
Pre-clean measurements (as per System Testing)
·
Post-clean measurements
·
Photographic records
·
Additional works carried out (if any)
·
COSHH data on any chemicals used
·
Recommendations for future cleaning requirements
·
Observations on the condition of the ductwork system
·
A sketch or schematic of the system indicating access
panel and testing locations and highlighting any uncleaned
areas with a written explanation as to why the area could not be
accessed/cleaned (see paragraph 7.6)
7.44
If specified, additional kitchen extract safety issues should also be reported
(as outlined in paragraph 7.26).
7.45
The Post-Clean Verification of Cleanliness report should assist to serve as
evidence of system status to insurance assessors, Environmental Health
Officers, landlord's agents, etc.